Dubai
Dubai
Abu dhabi
+971 4 3247500 Sun - Thu 08:00 - 5:30 No: FZJOA1517, JAFZA ONE PO BOX 18410, DXB
+971 2 6765979 Sun - Thu 08:00 - 5:30 P.O. Box : 33719, Abu Dhabi, UAE
Dubai
Dubai
Abu dhabi
+971 4 3247500 Sun - Thu 08:00 - 5:30 No: FZJOA1517, JAFZA ONE PO BOX 18410, DXB
+971 2 6765979 Sun - Thu 08:00 - 5:30 P.O. Box : 33719, Abu Dhabi, UAE
Leading Provider
Of Industrial Solutions
Number #1
Supplier in Middle East
Get A QuoteCatalogue

VICOTEC320 – Air Quality Tunnel Sensors

For the control of ventilation and for filter monitoring in road tunnels

The VICOTEC320 measures very small concentrations of NO2 and NO as well as the visibility and temperature in road tunnels simultaneously and quickly. using industry-proven components – without test gases for zero and reference point. An automated, cyclic adjustment of zero and reference point ensures exact values. The rugged housing even withstands thorough tunnel washing operations without any problems.

Description

The VICOTEC320 can be optionally equipped with an electrochemical CO measurement cell. This is useful for performing the plausibility checks which some tunnel standards (e.g., German RABT2006) recommend – even when NO2 is used as lead gas component.

Overview
Technical Specifications
Applications
Downloads

At a glance
  • Very low detection limits for NO and NO2
  • Automatic function monitoring and self-adjustment
  • Very rugged design in stainless steel
  • Automatic beam alignment between sender/receiver unit and reflector
Your Benefits
  • Energy and cost savings for ventilation control due to very low zero offset and accurate measurement
  • Low operational costs because no air aspiration of ambient air and no test gases are required
  • Low maintenance requirements due to long maintenance interval (approx. 1 year)

Measured values Visibility (K-value), NO, NO2, CO, temperature
Measurement principles Differential optical absorption spectroscopy (DOAS), transmittance measurement, electrochemical cell, Pt1000
Length of measuring path
10 m
20 m
Measuring ranges
K-value 0 … 15 km⁻¹ / 0 … 99 km⁻¹
NO 0 … 20 ppm / 0 … 45 ppm
NO2 0 … 1 ppm / 0 … 5 ppm
CO 0 … 100 ppm / 0 … 300 ppm
Temperature –25 … +55 °C
Response time (t90)
5 s … 360 s
Accuracy
Visibility (K-value) ± 0.8 km⁻¹
Ambient temperature
–25 °C … +55 °C
CO sensor –20 °C … +40 °C
Storage temperature
–25 °C … +75 °C
CO sensor –25 °C … +55 °C
Ambient pressure
700 hPa … 1,200 hPa
Ambient humidity
10 % … 95 %
Relative humidity, non-condensing
Electrical safety CE
Enclosure rating
IP69K
Analog outputs 6 outputs:
0 … 20 mA
Depending on device version
Digital outputs 4 relay contacts:
Depending on device version
Digital inputs 4 potential-free contacts
Ethernet
Function Connection to SOPAS ET software or OPC server
Dimensions (W x H x D)
Sender/receiver unit

Reflector unit

Connection unit

718 mm x 470 mm x 310 mm

617 mm x 278 mm x 245 mm

450 mm x 254 mm x 148 mm

Weight
Sender/receiver unit 20 kg
Reflector unit 9 kg
Connection unit 8 kg
Material Stainless steel 1.4571, powder-coated
Power supply
Voltage VICOTEC322, –323, –324: 115 V / 230 V
Frequency VICOTEC322, –323, –324: 50 Hz / 60 Hz
Power consumption VICOTEC322, –323, –324: ≤ 200 W
Test functions Automatic check cycle for zero and span point

Contamination check

Manual linearity check

Options CO sensor

Fields of applications

  • Monitoring of air quality in road tunnels
  • Ventilation control and filter monitoring in tunnels